A) Eight-hour working system: This working system is the basic working system. The agreed free air heating current Ith of the Modular Contactor is determined by this working system.
B) Intermittent periodic working system: The operating frequency of the AC contactor is 30 times/h and the load factor is 40%.
Action (operation) condition
In the ambient air temperature range of - 5 +60℃, when the suction coil of the contactor is applied with a quota to control the power supply voltage Us so as to heat it to a stable state, the contactor should be reliably closed at any voltage in the range of (85%~110%) Us, and released and disconnected between 75% and 20% of the rated control power supply voltage Us.
Product life
Mechanical life: The mechanical life of modular contactor is not less than 1 million times.
Electrical life: The electrical life of analog contactor is not less than 100,000 times.

Specifications 16A 20A 25A 40A 63A 100A
Rated current AC-7a 16 20 25 40 63 100
AC-7b 6 7 8.5 15 20 30
 Agreed heating current Ith(A) 25 25 25 63 63 100
Rated insulation voltage Ui(V) 500
Rated operating voltage Ue(V) 250V(1P/2P) 400V(3P/4P)
Number of main contacts 1P 1NO、1NC
2P 1NO1NC、2NO、2NC
3P 3NO、3NC
4P 2NO2NC、3NO1NC、4NO、4NC
Control power AC-7a 230V 3.5 4.5 5.5 9 14 22
400V 6.5 8 10 16 25 38
AC-7b 230V 1.4 1.6 2 3.5 4.5 6.5
400V 2.4 2.8 3.4 6 8 11
Electrical life(times) 10ten thousand
Mechanical life(times) 100ten thousand
Maximum number of switching operations per hour 30
Maximum number of switching operations per day 100
Quota control power supply voltage Us(V) AC 24/50Hz AC230/50Hz
frequency 50Hz/60Hz
Class of pollution 2
Rated impulse withstand voltage(Uimp) 2.5kV(4kV--12/24/48VAV)
Protection level
(IEC60529)
Contactor body IP20
Installed in distribution box Ip40
working temperature -5℃~+60℃
Storage temperature -40℃~+70℃
Hygrothermal resistance(IEC60068.1) 2-class(At 55℃,Relative humidity is 95%)
ELSV(Ultra-low Safety Voltage) 12/24/48 VAC
Product control meets the requirements of SELV (Safe Ultra-Low Voltage)

 

(1) The analog and digital control device has novel structure and compact volume.

(2) Installation orbiting, dimension modularization, safe use, can be combined with small circuit breakers installed in the control lighting box.

(3)The use of high-quality insulation materials greatly improves the safety.

(4) Beautiful appearance with working status indicator window.

(5)No noise