Installation Requirements & Safety Instructions
Installation Environment
- Install the equipment indoors only
- Ensure good ventilation
- Avoid wind, rain, and direct sunlight
Do NOT install the equipment in the following conditions:
- Where temperature or humidity exceeds operating limits
- Areas containing corrosive, flammable, or explosive gases
- Environments with excessive dust, salt, or metal powder
- Locations where water, oil, or chemical liquids may splash
- Areas subject to strong vibration or mechanical impact
- Near electromagnetic interference sources
Electrical & Environmental Protection
- Use appropriate shielding measures when installed near:
- Power lines
- Strong electric or magnetic fields
- Static electricity sources
- Electrical noise or AC contactors
Maintenance & Cleaning
- Perform regular maintenance to extend equipment life
-
Do not disassemble or repair the unit yourself
- Clean only with a soft, dry cloth
-
Do not use alcohol, gasoline, or organic solvents, as they may cause discoloration or deformation
Emergency Notice
If water ingress, smoke, unusual odor, or abnormal noise is detected:
- Immediately disconnect the power
- Stop using the device
- Contact the supplier or manufacturer promptly
Measuring Box Dimensions
-
Width: 350 mm
-
Height: 450 mm
(Custom pump and valve control available:
AC220V / AC380V, 2.2kW–5kW for high-power pumps or special applications)
Key Button Functions
1. Start
-
Starts the quantitative program after setting the target value
-
For multiple batches or different units (L, Kg, t), configure parameters first, then press Start
2. Pause
3. End
Product Overview:
This quantitative controller uses a high-performance PLC + HMI touch interface, compatible with:
It is designed for flow accumulation and precise dosing control.
Applications
-
Petroleum & chemical industries
-
Pharmaceutical production
-
Food & beverage processing
-
Quantitative filling, batching, loading, discharging, gas filling, and material dispensing
Key Features:
-
Intuitive visual HMI interface
-
Compatible with most flow meters and fluid media
-
Multiple measurement units: L, m³, Kg, t
-
Safety protections:
-
Data recording:
-
Cumulative reports for total and batch flow
-
Modbus RTU communication
-
Permanent data storage (retained after power loss)
Technical Specifications:
-
Display: 7-inch industrial touch screen
-
Controller: High-performance quantitative accumulation chip
-
Flow Input: Pulse signal (<5000 Hz, DC 24V)
-
Relay Outputs:
-
3 relays
-
3A @ 250VAC / 5A @ 24VDC
-
Power Supply:
-
Custom outputs available upon request
Terminal Descriptions (Main Connections)
-
485A / 485B: Modbus communication
-
24V / 0V: Flow meter power supply
-
Pulse Input: DC 24V pulse signal
-
Current Signal Input: Optional
-
L1 L2 L3 N: 3-phase power input (5-wire system)
-
U1 V1 W1: Water pump power output
-
Large Valve / Small Valve: Solenoid valve control
⚠️ Proper grounding is mandatory for both controller and pump to ensure safety and reduce interference.
Operation Interface:
Main Control Screen
-
Instantaneous Flow: Real-time flow display (read-only)
-
Quantitative Setting: Target dosing value
-
Quantification Times: 1–100 cycles
-
Current Quantitative Value: Real-time dosing progress
Control Buttons
System Notices
Parameter Settings Overview:
-
Flow meter coefficient (pulse mode)
-
Measurement range (current mode)
-
Large valve advance closing
-
Small valve advance closing
-
Pump advance shutdown
-
Pump start delay
-
Batch interval time
-
Cut-off alarm flow/frequency & delay
-
Density (for mass measurement)
-
Measurement units selection
-
Pulse mode / Current mode selection
Pulse mode is recommended for higher accuracy and wider applications.
Manual Control Mode:
Manual operation is available only when the system is stopped:
-
Large valve ON/OFF
-
Small valve ON/OFF
-
Water pump ON/OFF
⚠️ Pump can only start when at least one valve is open.
Data Recording:
-
Total accumulated flow
-
Last batch quantitative value
-
Automatic overwrite when memory is full
-
Manual data clearing available (irreversible)
Alarm History:
-
Records all system alarms
-
Useful for maintenance analysis
-
Alarm records can be cleared manually (cannot be recovered)
Common Faults & Solutions:
| Issue |
Possible Cause |
Solution |
| No response when pressing Start |
Quantification value or times = 0 |
Set values and restart |
| Flow mismatch |
Incorrect coefficient or installation |
Correct settings and reinstall flow meter |
| Hardware failure alarm |
Valve closed, wiring issue, no flow |
Check hardware and piping |
| Quantitative overshoot |
No advance closing set |
Adjust advance values |
Communication (Modbus RTU):
Supports reading and writing quantitative parameters, real-time flow, batch totals, and cumulative flow.