Item
|
Specifiation
|
|
Input
|
Inuput Voltage
|
1phase/3phase 220V:200V~240V
3 phase 380V-480V:380V~480V
|
|
Allowed Voltage fluctuation range
|
-15%~10%
|
|
Input frequency
|
50Hz / 60Hz,fluctuation less than 5%
|
|
Output
|
Output Voltage
|
3phase:0~input voltage
|
|
Overload capacity
|
General purpose application:60S for 150% of the rated current
Light load application:60S for 120% of the rated current
|
|
Control
|
Control mode
|
V/f control
Sensorless flux vector control without PG card(SVC)
Sensor speed flux vector control with PG card (VC)
|
|
Operating mode
|
Speed control,Torque control(SVC and VC)
|
|
Speed range
|
1:100 (V/f)
1:200( SVC)
1:1000 (VC)
|
|
Speed control accuracy
|
±0.5% (V/f)
±0.2% (SVC)
±0.02% (VC)
|
|
Speed response
|
5Hz(V/f)
20Hz(SVC)
50Hz(VC)
|
|
frequency range
|
0.00~2000.00Hz(V/f)
0.00~200.00Hz(SVC)
0.00~400.00Hz(VC)
|
|
Input frequency resolution
|
Digital setting: 0.01 Hz
Analog setting: maximum frequency x 0.1%
|
|
Startup torque
|
150%/0.5Hz(V/f)
180%/0.25Hz(SVC)
200%/0Hz(VC)
|
|
Torque control accuracy
|
SVC:within 5Hz10%,above 5Hz5%
VC:3.0%
|
|
V/f curve
|
V / f curve type: straight line, multipoint, power function, V / f separation;
Torque boost support: Automatic torque boost (factory setting), manual torque boost
|
|
Frequency giving ramp
|
Support linear and S curve acceleration and deceleration;
4 groups of acceleration and deceleration time, setting range 0.00s ~ 60000s
|
|
DC bus voltage control
|
Overvoltage stall control: limit the power generation of the motor by adjusting the output frequency to avoid skipping the voltage fault;
Undervoltage stall control: control the power consumption of the motor by adjusting the output frequency to avoid yaw failure
VdcMax Control: Limit the amount of power generated by the motor by adjusting the output frequency to avoid over-voltage trip;
VdcMin control: Control the power consumption of the motor by adjusting the output frequency, to avoid jump undervoltage fault
|
|
Carrier frequency
|
1kHz~12kHz(Varies depending on the type)
|
|
Startup method
|
Direct start (can be superimposed DC brake); speed tracking start
|
|
Stop method
|
Deceleration stop (can be superimposed DC braking); free to stop
|
|
Maincontrol function
|
Jog control, droop control, up to 16-speed operation, dangerous speed avoidance, swing frequency operation, acceleration and deceleration time switching, VF separation, over excitation braking, process PID control, sleep and wake-up function, built-in simple PLC logic, virtual Input and output terminals, built-in delay unit, built-in comparison unit and logic unit, parameter backup and recovery, perfect fault record,fault reset, two groups of motor parametersfreeswitching, software swap output wiring, terminals UP / DOWN
|
|
Function
|
Keypad
|
LED Digital keyboard and LCD keypad(option)
|
|
Communication
|
Standard:
MODBUS communication
CAN OPEN AND PROFINET( IN DEVELOPMENT)
|
|
PG card
|
Incremental Encoder Interface Card (Differential Output and Open Collector), Rotary transformer Card
|
|
Input terminal
|
Standard:
5 digital input terminals, one of which supports high-speed pulse input up to 50kHz;
2 analog input terminals, support 0 ~ 10V voltage input or 0 ~ 20mA current input;
Option card:
4 digital input terminals
2 analog input terminals.support-10V-+10V voltage input
|
|
Output terminal
|
standard:
1 digital output terminal;
1 high-speed pulse output terminal (open collector type), support 0 ~ 50kHz square wave signal output;
1 relay output terminal(second relay is an option )
2 analog output terminals, support 0 ~ 20mA current output or 0 ~ 10V voltage output;
Option card: 4 digital output terminals
|
|
Protection
|
Refer to Chapter 6 "Troubleshooting and Countermeasures" for the protection function
|
|
Environment
|
Installation location
|
Indoor, no direct sunlight, dust, corrosive gas, combustible gas, oil smoke, vapor, drip or salt.
|
|
Altitude
|
0-3000m.inverter will be derated if altitude higher than1000m and rated output current will reduce by 1% if altitude increase by 100m
|
|
Ambient temperature
|
-10°C~ +40°C,maximum 50°C (derated if the ambient temperature is between 40°C and 50°C)Rated output current decrease by 1.5% if temperature increase by 1°C
|
|
Humidity
|
Less than 95%RH, without condensing
|
|
Vibration
|
Less than 5.9 m/s2 (0.6 g)
|
|
Storage temperature
|
-20°C ~ +60°C
|
|
Others
|
Installation
|
Wall-mounted, floor-controlled cabinet, transmural
|
|
Protection level
|
IP20
|
|
cooling method
|
Forced air cooling
|
|
EMC
|
CE ROHS
|
Internal EMC filter
Complies with EN61800-3
Category C3
3rd Environment
|