WSM02-1 4-Channel Modbus Temperature Acquisition Module
The WSM02-1 Modbus Temperature Acquisition Module is an industrial temperature monitoring device designed to collect temperature measurements from multiple sensors and transmit the data to automation and monitoring systems.
Supporting 4-channel PT100 RTD sensors or 4-channel K-type thermocouples, the module provides a practical solution for industrial temperature acquisition, process monitoring, and automated control applications.
With its RS485 communication interface and Modbus RTU protocol, the WSM02-1 can be integrated with PLCs, industrial computers, HMIs, and compatible microcontroller systems.
Its wide DC operating voltage range and compact design make it suitable for industrial monitoring and distributed temperature measurement installations.
Key Features
-
4-Channel Temperature Acquisition: Supports simultaneous temperature monitoring from up to four sensors.
-
PT100 RTD Support: Compatible with PT100 resistance temperature sensors.
-
K-Type Thermocouple Support: Supports K-type thermocouple temperature measurement.
-
RS485 Communication: Suitable for industrial serial communication networks.
-
Modbus RTU Protocol: Enables integration with compatible PLCs, HMIs, and monitoring systems.
-
Wide Temperature Measurement Range: Supports high-temperature measurement using K-type thermocouples.
-
Wide Power Supply Range: Operates from 8V to 30V DC.
-
Low Power Consumption: Rated operating current below 120mA.
-
Multi-Device Networking: Suitable for RS485-based distributed monitoring systems.
-
Industrial Applications: Designed for temperature monitoring and data acquisition.
Technical Specifications
| Parameter |
Specification |
| Model |
WSM02-1 |
| Product Type |
Temperature Acquisition Module |
| Supply Voltage |
8–30V DC |
| Rated Operating Current |
Less than 120mA |
| Temperature Input Channels |
4 |
| Supported Sensor Types |
PT100 RTD / K-Type Thermocouple |
| PT100 Measurement Range |
-50°C to +450°C |
| K-Type Thermocouple Range |
-60°C to +840°C |
| PT100 Accuracy |
±0.2% (as stated in supplied specifications) |
| Thermocouple Accuracy |
±0.2% (excluding cold-junction compensation error) |
| Communication Interface |
RS485 |
| Communication Protocol |
Modbus RTU |
| Default Baud Rate |
9600bps |
| Default Device Address |
01 |
| Application |
Industrial Temperature Data Acquisition |
Sensor Compatibility
| Sensor Type |
Measurement Range |
Application |
| PT100 RTD |
-50°C to +450°C |
Industrial equipment and process monitoring |
| K-Type Thermocouple |
-60°C to +840°C |
High-temperature monitoring and industrial heating |
Note: Confirm the module's input configuration before connecting sensors. PT100 and K-type thermocouples use different measurement principles and wiring arrangements.
RS485 Modbus Communication
The WSM02-1 communicates through an RS485 serial interface using the Modbus RTU protocol.
Default Communication Parameters:
| Parameter |
Value |
| Interface |
RS485 |
| Protocol |
Modbus RTU |
| Baud Rate |
9600bps |
| Device Address |
01 |
| Communication Mode |
Serial |
The module can be connected to compatible Modbus master devices for temperature data acquisition.
Connection with PLC or Industrial Controller
- Connect the module to a regulated 8–30V DC power supply.
- Connect the RS485 communication terminals to the controller's corresponding RS485 interface.
- Connect compatible temperature sensors to the input channels.
- Configure the Modbus master with the module's communication parameters.
- Read the temperature values using the manufacturer's Modbus register map.
Connection with Arduino or ESP32
The module can be integrated with Arduino or ESP32 systems using a compatible RS485 transceiver module.
Required Components:
- Arduino or ESP32 Development Board
- RS485 Transceiver Module
- WSM02-1 Temperature Acquisition Module
- Compatible PT100 or K-Type Temperature Sensors
- Regulated DC Power Supply
The microcontroller operates as the Modbus master and reads temperature measurements from the acquisition module.
Applications
- Industrial Temperature Monitoring
- PLC Automation Systems
- Industrial Heating Equipment
- Temperature Data Logging
- Manufacturing Process Monitoring
- Multi-Point Temperature Measurement
- Industrial IoT Systems
- Furnace and Heating System Monitoring
- Laboratory Temperature Acquisition
- Remote Temperature Monitoring
Important Notes
-
Power Supply: Requires 8–30V DC. Do not connect directly to a 5V microcontroller power output.
-
Sensor Compatibility: Use PT100 RTD or K-type thermocouple sensors according to the module's supported input configuration.
-
RS485 Interface: A compatible RS485 transceiver is required when connecting to microcontrollers without built-in RS485 hardware.
-
Modbus Register Map: The manufacturer's register documentation is required to read and interpret temperature values correctly.
-
Accuracy: The stated measurement accuracy does not necessarily include sensor tolerance, wiring effects, or thermocouple cold-junction compensation errors.
-
Installation: Follow proper industrial wiring and grounding practices to minimize electrical interference.
-
Configuration: Confirm whether the supplied version supports PT100 and thermocouple inputs simultaneously or requires a specific input configuration.
Package Includes